TAIK ELECTRIC

Metering             
Solutions

News

T249T-Temperature Safeguard

2022-01-20

                                                          

 

                                               T249T-Temperature Safeguard

 

                             Features

                                          ● 4 Platinum RTD ,PT100 inputs

                                          ● 4 Designated relay contact outputs (Alarms/Trip/Fault)

                                          ● Extra 2 programmable relay contacts to be energized for starting up the cross flow fan

                                          ● 1 Analog output of Dc 4-20mA corresponding to the designated temperature channel

                                          ● The measured temperature unit available in either Fahrenheit or Celsius

                                          ● Communication interface via RS 485 , Modbus RTU

                                          ● Auto self-diagnostics for monitoring the internal faults caused on T249T

                                          ● Intelligent auto or manual operation

                                          ● All temperature measurements to be indicated simultaneously on the main displaying page

 

                             Specification

                                             Temperature imput : Max 4 channel RTD PT100 , option for Thermistor

                                             Dielectric strength : IEC 61010-1 , IEC 60688

                                             Power consumption : 5 - 15VA

                                             Sampling time : 0.3sec                                      

                                             IP enclosure : IP54 front , IP20 rear                    Max humidity : 95%

                                             Operating temperature : 0 - 60℃                       Auxiliary power supply : AC/DC 85-265V , 45~70 Hz

                                             Storage temperature : -10 - 70℃                        Accuracy : ±1℃