SIRO-MOD
Measurable: CO2, TVOC, PM, temperature and humidity.
Communication: RS485
Input: 24 VAC or VDC, ±10 %
Output voltage: 0–10 V/2–10 V / 0–5 V
Output current: 4–20 mA (optional)
LCD display and buttons(optional)
Siro-MOD is an indoor air quality transmitter with a modern design. The transmitter is available with several optional air quality sensors.
The modular device can be equipped with CO2 concentration and VOC measurements or PM measurement, temperature and humidity measurements. It offers easy installation and adjustment, several different model options and various output signals that are configurable separately for each measurement parameter.
Communication: RS485
Input: 24 VAC or VDC, ±10 %
Output voltage: 0–10 V/2–10 V / 0–5 V
Output current: 4–20 mA (optional)
Compensation function: On-site calibration of each measurement parameter (CO2, VOC, PM, rH, T) is possible
Measuring range:
CO2 0–2000 ppm / 400–2000 ppm
TVOC 0–30.0 ppm/ 0–10000 µg/m3
PM1/PM2.5/PM10: 0–50 μg/m³ / 0–500 μg/m³
Temperature 0...50 °C
Relative humidity 0–100 %rH
Accuracy:
CO₂: ±40 ppm + 3 % of reading (typical),
additional ±60 ppm for first weeks
Relative humidity: ±2.2 % rH (typical at 20 °C, 30 % rH)
Temperature: ±0.4 °C (typical at 20 °C)
VOC: ±15 % of reading (typical)
*VOC sensor is tuned for typical IAQ Mix of 22 VOCs as defined by Mølhave et al. (1997)
PM:
0…100 μg/m3:
PM2.5: ±15 μg/m3(at 25 ⁰C ±5 ⁰C)
PM1/PM10*: ±25 μg/m3 (at 25 ⁰C ±5 ⁰C)
100…1000 μg/m3:
PM2.5: ±15 % (at 25 ⁰C ±5 ⁰C)
PM1/PM10*: ±25 % (at 25 ⁰C ±5 ⁰C)
*PM1 and PM10 values are calculated from PM2.5 measurement reading with the default particle distribution.